Specifications | |
---|---|
Amperage | 40A |
Maximum Voltage | 48V DC |
Mounting | Surface Mount |
Circuit Breaker Type | Thermally responsive Bi-metal blade |
Terminal Stud | M6 (accepts 1/4" Ring Terminal) |
Terminal Stud Torque | 50 in-lb (5.65 Nm) |
Interrupt Capacity | 3000A @ 48V |
Minimum Operating Temperature | -40° C |
Maximum Operating Temperature | 85° C |
Circuit Breaker Class | Type III - switchable/manual reset - trip free |
Weight | 0.50lb (0.23 kg) |
Optional Accessories | ||
---|---|---|
2719 | MaxiBus Insulating Cover for PN 2127 and 2128 |
Meets the following Regulatory Specifications |
---|